LoginFuel Type | |
---|---|
Fuel Type | Carpentry Waste, Approved Wood Waste, Wood pellet, Wood chip |
Chimney Specification | |
Flue Spigot External Diameter | 250 mm |
kW Power | |
kW power output | 200 kW |
Directly fed air-cooled 2-zone step grate for constant clean combustion with automatic firebox deashing for the highest comfort;
optional under grate deashing
Automatic fly ash removal
Combine modular combustion chamber with fired bricks for long life operation.
The hot temperature zone between grate and combustion chamber for consistent performance control with primary / secondary air and tertiary air servo motors,
Combustion chamber temperature sensor and lambda probe for compliance lowest emission values and highest efficiencies
Automatic ignition with integrated level monitoring and Stainless-steel ignition tube
Automatic cleaning of the heat exchanger tubes
Vacuum control with frequency converter and induced chimney fan for an economical operation
Feeding VBZ 160 - Solid 4-chamber bucket wheel Ø250mm cast as backfire protection Common drive with discharge for particularly energy-saving operation
Replaceable counter-blade for shortening long fuel sections
Stoker screw with Ø140mm for constant and energy saving material dosage
Level indicator in the dosing transition to the stoker screw
Individually adjustable tilt and swivel range for optimal Adaptation to installation site
Suitable for wood chips (max 240 kW) up to P45S (formerly G50), Pellet A1 (DIN EN ISO 17225-4 / -2)
Tested gas tightness
Control cabinet EMD-C215 Exclusive
400 V control cabinet with wall-mounted housing 100 x 100 cm,
including fastening material, emergency stop switch, main switch,
Operating switch, operating and fault light
PLC control with 16 digital inputs and outputs, measured value recording via CAN module with 8 inputs and 4 outputs 8x40 characters display with clear menu
Cable bushing by means of a choke nipple from above, terminal strip with screw terminals, control transformer 24 V DC / 24 V AC / 12 V AC
Motor contactors for charging, discharging, ash removal, relays
Current transformer for reversing the feed
Automatic switch-on after power failure
Integrated buffer storage management, residual heat utilization,
Combustion and capacity control
Connection for external storage room limit switch, input for external
Request command, output for external fault message
Program extension for the connection of further drive motors,higher-level control, peak load connection
-Optionally available: connection option for HDG remote maintenance, PC / Web visualization or remote alarm,